Simulation evaluates data centre cooling
American Power Conversion helped solve a potential overheating problem in a customer's new data centre by using simulation to evaluate alternative designs prior to installing the equipment.
American Power Conversion (APC) helped diagnose and solve a potential overheating problem in a customer's new data centre by using simulation to evaluate alternative designs prior to installing the equipment.
The simulation showed that the customer's original design would result in overheating if a single computer room air conditioner (CRAC) failed for even a short period of time.
"We used Flomerics' Flovent computational fluid dynamics (CFD) software to identify the problem, evaluate its root cause, and develop a new design that can withstand loss of any one single piece of equipment", said Ben Steinberg, Senior Applications Engineer for APC.
Steinberg used Flovent to model the geometry of the data centre and thermal and airflow characteristics of the servers and cooling units.
"Flovent is designed specifically for modelling heating and cooling applications so it is both easier to use and more powerful than general purpose CFD codes when evaluating data centre cooling", Steinberg said.
"Flovent also has a team of support engineers that provide excellent support because they have a very good understanding of data centre cooling issues".
Like most new data centres, this one made extensive use of blade servers, which greatly increase the amount of computing power that can be packed into a given amount of space but at the same time generate much more heat than traditional servers.
The customer's initial design positioned the equipment in three rows with one CRAC in each row.
Steinberg ran a steady state simulation with all CRAC units operating and then removed the CRACs from the model one after another and reran the simulation.
The results showed that when one particular CRAC unit was removed, temperatures quickly reached the unacceptable 32C level.
Steinberg suggested adding a fourth row of equipment with a fourth CRAC unit.
He pointed out that the fourth row would provide each hot aisle with one CRAC unit on each side of the aisle, providing redundancy in case one unit failed.
In order to confirm this assumption, Steinberg modified the Flovent model to add the fourth row of equipment and the fourth CRAC.
The results showed that regardless of which CRAC was removed, temperatures remained at safe levels of between 24 and 27C throughout the data centre.
Steinberg showed these results to the owner and the owner made the decision to go with the new design and purchase the four CRACs from APC.
"It would have been extremely costly to install the equipment in the data centre, run tests, and then discover that it would not properly cool the servers in the event of an equipment failure", Steinberg said.
"But it would have been far more costly for the customer to have its data centre go down because of cooling problems".
"This helps explain why we run simulations for many of our proposals".
"Simulation provides a fast, relatively inexpensive, and accurate method of evaluating data centre cooling performance without going to the time and expense required to actually install and test the equipment".
Not what you're looking for? Search the site.
Tel +44 20 8941 8810
-
Flovent software determines TDV guidelines
Aecom consultants used Flovent software from the Mentor Graphics Mechanical Analysis Division to determine the viability of and guidelines for the use of thermal displacement ventilation (TDV). -
Simulation is cool answer for supercomputer lab
CFD simulations save money by determining exactly how much cooling capacity is required to handle current and projected thermal loads. -
Ancis optimises data centre cooling with Flovent
Ancis recently helped a major telecom firm develop a greatly improved heating, ventilating, and air-conditioning (HVAC) design using Flomerics' Flovent computational fluid dynamics -
Thermal simulation helps platform beat ATCA specs
Design team leader claims that thermal simulation is like having X-ray vision. -
Thermal simulation cuts potting costs in half
The Flopack web-based wizard quickly produces accurate models of integrated circuits and other components.
Categories
- Active Components (11,917)
- Passive Components (2,949)
- Design and Development (9,394)
- Enclosures and Panel Products (3,246)
- Interconnection (2,841)
- Electronics Manufacturing, Production, Packaging (3,055)
- Industry News (1,898)
- Optoelectronics (1,616)
- Power Supplies (2,297)
- Subassemblies (4,551)
- Test and Measurement (4,956)