Visit the Unipower Europe web site

Switchers certified for medical applications

An Ultimate Renaissance product story
Edited by the Electronicstalk editorial team Mar 19, 2002

Ultimate Renaissance has a range of AC/DC switching power supplies certified to IEC601 and UL2601 safety standards for Type-B non-patient-connected medical equipment.

Ultimate Renaissance has a range of AC/DC switching power supplies certified to IEC601 and UL2601 safety standards for Type-B non-patient-connected medical equipment.

The EOS MVLT110 Series are 110W open-frame PSUs combining extremely small size and high efficiency to raise system reliability, save product development costs and give designers more flexibility.

At 76.2 x 126.9 x 27.2mm and 250g total weight, power density is 6.85W/in3.

By achieving 4000V isolation voltage and leakage current 0.1 and 0.5mA for a single fault, specified by the IEC and UL medical safety standards, the MVLT110 Series is suitable for use in non-patient-connect medical equipment, and also industrial and laboratory equipment.

Applications include touch screen displays, laboratory and analysis systems, medical research equipment, hospital data systems, health care information systems, dental equipment and outpatient equipment.

The MVLT110 Series includes single output and four-output models.

The single output MVLT110-1301 is a 5V/18.0A single-output PSU.

Further single output versions offer 12, 15, 24 and 48V outputs.

The four-output models offer a combination of +3.3 or +5V 15.0A primary output with -5, +/-12, +/-15 and +24V secondary outputs.

One example, the MVLT110-4304, combines 3.3V/15.0A primary output with +5V/3.0A and +/-12V/0.8A outputs.

Designed for mains powered applications from 90 to 264V, the MVLT110 Series operates at 85% efficiency, at maximum full load input current 2.6A RMS.

Output characteristics include 18ms hold up time in 230V applications, and 0.3% line regulation.

Load regulation and voltage set point accuracy for the V1 output is +/-1%.

Overload protection, short circuit protection and power fail/power good signals are all included.

Nominal operating temperature range is 0 to 50C, extending to 70C with 2.5%/C derating.

MTBF is greater than 200kh.

In addition to meeting worldwide UL2601, EN60601, and IEC601 medical safety standards, the MVLT110 Series is also CE approved and FCC certified.

Not what you're looking for? Search the site.

Back to top Back to top

Contact Ultimate Renaissance

Related Stories

Contact Ultimate Renaissance

 

Newsletter sign up

Request your free weekly copy of the Electronicstalk email newsletter ...

Visit the Unipower Europe web site

Search by company

A Pro-talk Publication

A Pro-talk publication